SAFE 10Y30-BASIC is a new generation of standalone smoke alarm with breakthrough detection using a dual-spectrum, dust-resistant optical chamber and SIC technology for temporarily silencing the alarm using an IR remote control. Power is supplied by an integrated lithium battery (built in, non-replaceable) guaranteeing exceptionally long operation of the device of more than 10 years and an extended 7-year warranty on both the battery and the device itself. The SAFE 10Y30-BASIC fire alarm sets a new level of standard in the fire safety of residential buildings.
Foreword
General
This user manual describes the installation, functions and operation of the SAFE 10Y30-BASIC standalone smoke alarm (hereinafter the “alarm”). The alarm works completely independently, with no need to connect to a Hub or mobile app. Read the manual carefully before using the device and keep it for future reference.
Safety instructions
The following signal words may appear in the user manual:
| Signal word | Meaning |
|---|---|
| NEBEZPEČÍ | Indicates a high potential hazard which, if not avoided, may result in death or serious injury. |
| VAROVÁNÍ | Indicates a medium or low potential hazard which, if not avoided, could result in minor or moderate injury. |
| UPOZORNĚNÍ | Indicates a potential risk which could lead to property damage, data loss, reduced performance or an unpredictable result. |
| TIP | Provides methods to help you solve a problem or save time. |
| POZNÁMKA | Provides additional information, such as emphasis or a supplement to the text. |
Revision history
| Version | Revision content | Release date |
|---|---|---|
| V1.0.0 | First release. | September 2026 |
| V1.0.1 | Colours according to the FireSAFE brand (red). | October 2026 |
About the manual
- The user manual serves as a reference only. Minor differences may occur between the information provided and the product.
- We are not liable for damage resulting from use of the product in a manner that is not in accordance with the instructions in the user manual.
- The manual will be updated in line with the current laws and regulations of the relevant countries. For detailed information, see the printed user manual or visit our website. The electronic and printed versions may differ in minor details.
- All designs may be changed without prior written notice. As a result of product updates, certain differences may appear between the product and the information in the manual.
- Printing errors or deviations may occur in the description of functions, operations and technical data. In case of doubt or dispute, we reserve the right of final interpretation.
- All trademarks, registered trademarks and company names in the manual are the property of their respective owners.
- If any problems occur while using the device, visit our website, or contact your supplier or customer service.
Operating requirements
- Under no circumstances ignore the alarm's sounding – such behaviour could lead to serious injury or death.
- Exposing the alarm to high or low temperatures or to high humidity can significantly reduce battery life.
- Before using the device, make sure the alarm is correctly installed in the mounting bracket and that its power has been activated.
- Use the device in accordance with the instructions given for the operating environment.
- Transport, use and store the device under the humidity and temperature conditions permitted by the manufacturer.
- Do not expose the product to water or moisture, or to dripping or splashing water.
- Do not insert any objects into the ventilation openings of the product, do not cover the product, and take care to prevent water or other liquid from entering the alarm.
- This fire alarm is intended only to indicate the presence of smoke – it is not intended to detect carbon monoxide (CO), flammable gases or other hazards.
Installation requirements
- Incorrect installation and operation of this device will prevent it from functioning correctly and consequently from responding to the danger of fire.
- When working at height, follow all safety procedures and use the required protective equipment intended for this purpose.
- Do not expose the product to direct sunlight, extreme cold, humidity or sudden changes in temperature.
- Before using the device, you must stick on it the information label “CAUTION! – Battery is not replaceable, see user manual” in your language.
- If dusty construction work is taking place at your premises, you should remove the device from the mounting bracket to prevent it from becoming soiled or the detection chamber from being contaminated by dust particles. If this is not possible, cover the alarm for the duration of the work (e.g. with a plastic bag) to prevent contamination by dust. A covered alarm cannot detect smoke, so uncover it every day after work has finished.
- Installation and handling of this device must always comply with local electrical safety requirements, requirements for protection against electric shock and other relevant regulations.
Functional elements
- LED indicator – visually signals the states of the individual modes of the device (see Signalling).
- Buzzer – alarm volume 85 dB (A) at a distance of 3 m.
- TEST/Silence button – verifies the functionality of the device; also used to temporarily silence the acoustic alarm signal.
- Battery location – on the back of the alarm, built-in battery, not user-replaceable.
Principle of operation
The smoke alarm is designed for continuous monitoring, detection and signalling of smoke. The device uses advanced split-spectrum photoelectric chamber technology, a built-in loud alarm buzzer, fast response to hazard detection combined with high sensitivity, stable performance and high resistance to false alarms. As soon as the smoke concentration around the sensor reaches the alarm level, the alarm immediately triggers an acoustic and visual alarm signal to inform the user of the approaching danger.
Dual-spectrum smoke chamber
A dual-spectrum optical sensor with blue and infrared LED sources of different wavelengths is integrated into a dust- and insect-resistant smoke detection chamber. The chamber design with a direct link to the microprocessor AI SAFE offers the most reliable detection method, which, combined with a predictive algorithm, enables measurement of the concentration of microparticles directly in the air in real time. This technology can determine the size of volatile particles inside the optical chamber and respond only to a real threat in the form of smoke, while ignoring the similar composition of water vapour or other fumes.
Protection against false alarms
The AI SAFE microprocessor was developed on the basis of a detailed analysis of the combustion properties of materials and works with a predictive algorithm that compares data from the dual-spectrum optical sensor and filters potential false alarms in real time. If the recorded data correspond to liquid particles of water vapour or other types of fumes, the alarm will not react. However, if the dynamics of the data pattern correspond to the real parameters of the solid smoke particles of a fire, the alarm immediately triggers a fire alarm.
SIC technology – remote silencing with an IR remote control
The alarm has a combined button with TEST and Silence functions, which is used both for testing and verifying the correct functioning of the device and for temporarily silencing the alarm. If you know the cause of the fire alarm activation and need to silence the loud acoustic signalling, there is no need to reach the alarm directly – the technology SIC allows remote silencing of the acoustic signalling by pressing any button on an ordinary IR remote control (most remote controls for household appliances, for example for a TV).
IZOVAX protection for damp spaces
The alarm's electronic components and printed circuit board are coated with an insulating and protective layer of varnish with nanoparticles IZOVAX. Thanks to this, and to the dual-spectrum optical chamber technology, which distinguishes smoke particles from water vapour, the device can, unlike conventional fire alarms, also be installed in very humid environments (near bathrooms, drying rooms, kitchens or utility rooms).
Guaranteed operating performance for a whole decade
Power is supplied by an integrated 3 V CR123A lithium battery (built in, non-replaceable), guaranteeing exceptionally long operation of the alarm of more than 10 years. The power battery is activated when the alarm is placed and locked into the mounting bracket. After 10 years of protection, and 30 days in advance, the alarm announces the end of its life and automatically warns that it needs to be replaced (see End of life).
Signalling
| LED indication / sound | Event |
|---|---|
| Short buzzer beep + red LED flash | Device activation after insertion into the mounting bracket; a short initialisation follows |
| Green LED flashes 1× every 60 s | Standby (operating) mode – everything is in order |
| Short buzzer tone + red LED flash | Short press of the TEST/Silence button – confirmation of functionality |
| Red LED flashes 1× per second + buzzer beeps 1× per second (repeatedly) | Fire alarm triggered |
| Red LED flashes 1× per second, no sound | Temporary alarm silencing active (using the TEST/Silence button or the IR remote control – SIC technology) |
| Red LED flashes 2× every 60 s | Device fault – the alarm is not functional, clean it and test it (see Maintenance) |
| Red LED flashes 1× every 60 s + buzzer beeps 1× every 60 s (for 30 days) | Low battery – end of life is approaching; the alarm must be replaced with a new one |
Choosing the installation location
Smoke alarms should ideally be installed in all rooms of the house except kitchens, bathrooms and garages. At least one alarm should be placed on every floor of the house, including the staircase. Place the alarms where you can hear them even when asleep – for example in the hallway in front of the bedroom. Install an alarm on the ceiling of each bedroom and in the hallway in front of the bedroom.
- If the hallway is longer than 9 m, install an alarm at both ends.
- If you have a multi-storey house, install alarms in the same way on every floor – you will thus also be protected against smoke rising through the stairwell from the lower floor. In the basement, install the alarm on the ceiling at the bottom of the stairs.
Where not to install the alarm
- In bathrooms and kitchens – water vapour and steam from food can trigger a false alarm.
- In a garage – the alarm could react to exhaust fumes from vehicles.
- In places where the ventilation openings around the alarm are not freely accessible – do not cover them or otherwise seal them.
- Do not use aerosol products near the alarm.
Ceiling or wall installation
The manufacturer allows the device to be installed both on the ceiling and on a side wall, the preferred mounting location being central installation on the ceiling. When installing on the ceiling, install the alarm at a distance of at least 500 mm from the corners of the room. When mounting on a side wall, position the device so that its upper part is at least 100 mm and at most 305 mm below the ceiling level.
Installation on a sloping ceiling
If the ceiling slope is less than 45°, a suitable distance from the apex is at least 500 mm. If the slope is greater than 45°, a wooden base must be installed (not included in the package).
Installing the alarm
- Choose a suitable location for installing the fire alarm (see Choosing the installation location).
- At the installation location, drill holes (⌀ 6 mm) using the mounting bracket. Insert wall plugs into the prepared holes.
- Fix the bracket with self-tapping screws.
- Stick the information label in your language (“CAUTION! – Battery is not replaceable, see user manual”) on the device.
- Insert the alarm into the mounting bracket and turn it clockwise until it locks into position.
Function test and Silence
After installing the device, or during its regular maintenance, an alarm test must be carried out to prove its functionality.
- Briefly press the button TEST/Silence.
- The buzzer sounds an acoustic tone and the LED indicator flashes red; a pause follows, then the buzzer beeps 3 times in a row accompanied by a flash of the red LED indicator, another pause and one more repetition.
As soon as the smoke concentration reaches a predetermined value, the alarm sounds. The acoustic signalling can be temporarily silenced if necessary for approx. 9 minutes:
- by briefly pressing the button TEST/Silence directly on the alarm, or by
- pressing any button on an ordinary IR remote control (SIC technology) – there is no need to physically reach the alarm.
If the concentration of smoke particles subsequently falls below the predetermined value, the alarm automatically returns to normal operating mode. Otherwise, after the silence time has elapsed, the alarm returns to alarm mode.
| Problem | Solution |
|---|---|
| The alarm does not sound the buzzer during testing | If you are testing immediately after the first activation, wait a few seconds for the alarm to initialise. Make sure you have pressed the TEST/Silence button correctly. |
| The alarm chirps intermittently | Check that the device is correctly positioned (see Choosing the installation location) and carry out maintenance (see Maintenance). |
| The LED indicator flashes red and the buzzer beeps every 60 s | The alarm's battery is depleted – the built-in battery cannot be replaced; the alarm must be replaced with a new one. |
If the device test is not completed successfully, send the alarm in for a warranty claim.
Maintenance
- Test the alarm by pressing the TEST/Silence button at least once a week.
- Clean the alarm at least once a month: remove it from the bracket (by turning it anticlockwise), use a vacuum cleaner to remove accumulated dust particles through the ventilation openings and wipe the outside with a damp cloth. Do not use cleaning agents or solvents – there is a risk of sensor contamination and loss of warranty. After cleaning, install the alarm back and test it with the TEST/Silence button.
- Do not paint the device – paint may seal the air circulation openings and impair the sensor's ability to detect smoke.
- Do not place the alarm in places prone to vibration and shocks.
- Do not expose the alarm to excessive pressure, impacts, dust, high temperature or humidity.
- Do not place sources of open flame (lighter, candle, etc.) on or near the device.
- Do not install the alarm in places where sufficient air flow is not ensured, near fans or other devices connected with air conditioning.
- If dusty construction work is taking place nearby, temporarily remove the alarm from the bracket or cover it for the duration of the work (e.g. with a plastic bag) to prevent contamination of the detection chamber. A covered alarm does not detect smoke – always uncover it after the work has finished.
- Do not disassemble the alarm or interfere with its internal electrical circuits – any such interference leads to loss of the warranty. Servicing is carried out only by the manufacturer's authorised service centre.
End of life
The battery of the SAFE 10Y30-BASIC alarm is built in and not user-replaceable. The alarm must be replaced with a new one after 10 years from the date of installation – the replacement date is shown on the information label on the back of the alarm. The alarm signals that its end of life is approaching (decline in battery capacity) by flashing the red LED indicator once accompanied by one beep of the buzzer at regular 60-second intervals for 30 days before the battery is fully depleted.
Technical specifications
| Detection parameters | |
| Detection type | Smoke, fault, low battery capacity |
| Sensor | Photoelectric – dual-spectrum (blue + IR LED) |
| Microprocessor | AI SAFE with predictive algorithm |
| Preset alarm value | 0.2–0.3 dB/m |
| Detection area | 20–40 m² (for a room height up to 8 m) |
| Protection against false alarms | Yes (AI SAFE predictive algorithm) |
| Signalling | |
| Acoustic | 85 dB at a distance of 3 m |
| Visual | LED indicator (dual) |
| Silence function | Yes – TEST/Silence button, IR remote control (SIC technology) |
| Silence time | approx. 9 min |
| General | |
| Order code | SAFE 10Y30-BASIC |
| EAN code | 0703123017930 |
| Power supply | 3 V DC, 1× CR123A lithium battery (integrated, non-replaceable) |
| Current consumption | Standby mode ≤ 15 µA; in alarm ≤ 35 mA |
| Battery / device life | 10 years |
| PCB protection | IZOVAX insulating and protective varnish layer with nanoparticles |
| Operating temperature | −10 °C to +55 °C |
| Operating humidity | up to 95 % RH (non-condensing) |
| Storage temperature / humidity | −20 °C to +60 °C, 5–95 % RH (non-condensing) |
| Dimensions | ⌀ 81.5 mm × height 51.6 mm (with mounting bracket) |
| Weight | 110 g (with battery) |
| Mounting method | On a ceiling or wall (mounting material included in the package) |
| Type of installation | Indoor |
| Certification | EN 14604:2005+AC:2008; CE 1008-CPR-MC 69267856; ISO 7731; AS 3786:2014+A1+A2 |
| Warranty | 7 years (on the device and battery) |
Package contents
- Smoke alarm – 1 pc
- Self-tapping screw – 2 pcs
- Wall plugs – 2 pcs
- Mounting bracket – 1 pc
- User manual with a set of information labels – 1 pc
Safety notices
- Read these instructions carefully before use and keep them for future reference.
- Under no circumstances ignore the alarm's sounding – such behaviour could lead to serious injury or death.
- Exposing the alarm to high or low temperatures or to high humidity can significantly reduce battery life.
- Before using the device, make sure the alarm is correctly installed in the mounting bracket and that its power has been activated.
- Transport, use and store the device under the humidity and temperature conditions permitted by the manufacturer.
- Do not expose the product to water or moisture, or to dripping or splashing water. Do not insert any objects into the ventilation openings and do not cover the product.
- This alarm is intended only to indicate the presence of smoke – it is not intended to detect carbon monoxide (CO), flammable gases or other hazards.
- Installation and handling of the device must always comply with local requirements for electrical safety and protection against electric shock.
- Do not disassemble or modify the alarm – in case of a fault, contact support; servicing is carried out only by the manufacturer's authorised service centre.
- The device is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities without supervision or instruction by a responsible person. Make sure children do not play with the device.
- Do not dispose of the product with general municipal waste or throw it into a fire – hand it in for recycling in the electrical equipment take-back system.
What to do in the event of a fire alarm
- Wake small children and leave the endangered area immediately along a pre-planned escape route. Do not waste time getting dressed or collecting valuables.
- Never open interior doors without touching them first. If the door is hot or smoke is coming through the gaps, do not open it and use an alternative escape route.
- If you enter an area with a concentration of smoke, move low to the ground and breathe slowly, ideally through a dampened cloth.
- Once you are outside the building, go to the designated evacuation point and make sure everyone is present. Do not return to the building until the danger has passed.
- Contact the emergency services only once you are safe.
Warranty
The manufacturer provides a warranty on the SAFE 10Y30-BASIC alarm 7 years from the date of sale, covering both the device and the integrated battery. Under the warranty, the manufacturer's obligation is limited to repairing or replacing the alarm, or any part of it, in which a defect in material or workmanship is found.
The warranty becomes void if the product has been damaged, altered, misused or modified after purchase, or if it has stopped working as a result of poor maintenance or incorrect placement. The warranty does not affect your statutory rights.
In case of problems with the device, first contact technical support – most situations can be resolved remotely.
Need help?
SAFE HOME europe technical support:
E-mail: info@safe-home.eu · Telephone: (+420) 581 222 262
Web: www.smart-safe.eu