FireSAFE / Wireless products

Wireless heat alarm compatible with the FireSafe app
SAFE 10YHT-RF

User manual

Updated 13 October 2026

Product page Datasheet (PDF)
The SAFE 10YHT-RF alarm

SAFE 10YHT-RF is a new-generation wireless heat alarm designed to detect fires that are not accompanied by smoke, providing early warning of imminent danger when a rapid rise in temperature is detected in the monitored space. It features SIC technology for temporarily silencing the alarm using an IR remote control and can work as part of the FireSafe fire safety system with the support of the FireSafe Hub, or completely standalone. Power is supplied by an integrated lithium battery (built in, non-replaceable) with guaranteed operation of more than 10 years and an extended 10-year warranty on both the battery and the device itself.

1 000 mradio signal range
85 dBacoustic fire alarm
24 hactive protection every day
24max. linked devices
10 yearslife and warranty
54–65 °Calarm temperature range
CONNECTED wireless linking of FireSafe devices
CThermistor with intelligent algorithm
SIC remote alarm silencing with an IR remote control
Radio signal range up to 1000 m
Battery operation for up to 10 years
IZOVAX protection

Foreword

General

This user manual describes the installation, functions and operation of the wireless heat alarm (hereinafter the “alarm”). Read the manual carefully before using the device and keep it for future reference.

Safety instructions

The following signal words may appear in the user manual:

Signal wordMeaning
NEBEZPEČÍIndicates a high potential hazard which, if not avoided, may result in death or serious injury.
VAROVÁNÍIndicates a medium or low potential hazard which, if not avoided, could result in minor or moderate injury.
UPOZORNĚNÍIndicates a potential risk which could lead to property damage, data loss, reduced performance or an unpredictable result.
TIPProvides methods to help you solve a problem or save time.
POZNÁMKAProvides additional information, such as emphasis or a supplement to the text.

Revision history

VersionRevision contentRelease date
V1.0.0First release.September 2026
V1.0.1Colours according to the FireSAFE brand (red).October 2026

About the manual

Important precautions and warnings

This section contains information on the correct handling of the product, risk prevention and prevention of property damage. Read it carefully before using the device and follow the instructions provided while using it.

Operating requirements

VAROVÁNÍ
UPOZORNĚNÍ

Installation requirements

VAROVÁNÍ
UPOZORNĚNÍ

Functional elements

Functional elements of the SAFE 10YHT-RF alarm – numbered diagram of the front and back
Functional elements of the SAFE 10YHT-RF alarm
  1. LED indicator – visually signals the states of the individual modes of the device (see States and signalling).
  2. Test / Silence button – verifies the functionality of the device; also used to temporarily silence the acoustic alarm signal.
  3. Buzzer – alarm volume 85 dB (A) at a distance of 3 m.
  4. Battery location – built-in battery, not user-replaceable.

Principle of operation

The wireless heat alarm is designed to detect and signal a rise in temperature caused by a fire that is not accompanied by smoke, and provides early warning of imminent danger when a rapid rise in temperature is detected in the monitored space. The fixed alarm trigger temperature in Class A1 is calibrated to within the range +54 °C to +65 °C. As soon as the heat level around the thermistor sensor reaches the alarm level, the alarm immediately triggers an acoustic and visual alarm signal. The alarm includes an integrated RF module which, thanks to the CONNECTED function, makes it possible to wirelessly link two or more FireSafe alarms (maximum 24 units) and create an interlinked network – when an alarm is raised, the alarm immediately passes the event on to the other devices in the network. A FireSafe Hub can be added to the network, which, thanks to its internet connection, allows convenient setup and control of the whole system, including remotely, using the app of the same name, and immediately informs the user by push notifications if danger is detected. The alarm can also work completely standalone, without connection to a Hub.

Class A1 thermistor sensor

The SAFE 10YHT-RF alarm has been designed for a wide range of applications and environments in which reliable fire detection cannot be ensured using conventional optical technologies. It provides an effective solution for detecting fires with a rapid rise in temperature during combustion, or slowly developing fires that cause a rise in temperature in the monitored space. For detection it uses an intelligent predictive algorithm combined with a Class A1 thermistor sensor, designed to sit outside the housing to ensure an immediate response without further delay. The measurement interval is a repeating 10 s cycle.

Protection against false alarms

The AI SAFE microprocessor was developed on the basis of detailed analysis of the combustion characteristics of materials and works with a predictive algorithm that compares the measured temperature and its rate of rise with predictive patterns in real time. If the dynamics of the data pattern match the actual temperature parameters of a developing fire, the alarm immediately triggers a fire alarm.

SIC technology – remote silencing with an IR remote control

The alarm has a combined TEST and Silence button, which is used both to test and verify that the device is working correctly and to temporarily silence the alarm. The SIC technology allows the acoustic signal to be silenced remotely by pressing any button on an ordinary IR remote control (most remote controls for household appliances, such as a TV), without having to reach the alarm itself.

IZOVAX protection for demanding environments

The electronic components and printed circuit board of the SAFE 10YHT-RF alarm are coated with an insulating and protective layer of varnish containing nanoparticles IZOVAX. Thanks to this, and to the thermistor sensing technology, unlike conventional optical fire alarms, the device can also be installed in a wide range of challenging environments (bathrooms, drying rooms, saunas, swimming pools, kitchens, garages, boiler rooms, workshops, storerooms, laboratories…) where moisture, fumes, chemicals, dust or the presence of smoke particles could cause false alarms in conventional alarms.

FireSafe wireless communication

The device can be linked by pairing only with wirelessly linkable FireSafe elements; it is not intended for communication with devices of other brands or manufacturers.

Interconnection

This device can be linked by pairing only with wirelessly linkable FireSafe elements. It is not intended for communication with wirelessly linkable devices of other brands or manufacturers.

Before you start linking the devices wirelessly, make sure all devices are activated and powered. To activate the alarm, insert it into the mounting bracket and turn it clockwise until it locks into the fixing position.

Make sure that several wireless elements are paired one after another, linking only two elements with each other at any one time. Otherwise the link may fail or one of the devices may malfunction.

How to link the devices

  1. Entering pairing mode – on the first device to be paired, press the TEST/Silence button 4× briefly in succession (the interval between presses must be shorter than 1 second). The device emits 1 short acoustic tone and the LED indicator flashes red at short regular intervals (approximately once every 0.5 s) to indicate that the device has entered pairing mode.
  2. Connecting the second device to the network – on the second device, press the TEST/Silence button 2× briefly in succession (interval shorter than 1 s). The device emits 1 short acoustic tone and the red LED indicator flashes approximately once every 0.25 s to indicate transmission mode.
  3. Confirming pairing – after the two devices have been paired successfully, the second device emits a short sound signal and the LED indicator flashes green. The green indicator flashes until device 1 leaves pairing mode, or until you press the TEST/Silence button on device 2 to switch to normal mode.
  4. Connecting a third and further devices – if device 1 is still in pairing mode, press the TEST/Silence button 2× briefly in succession on the next device and repeat the procedure. In the manner described, up to 24 wireless FireSafe devices can be linked into the network.
  5. Checking functionality – after connecting all wireless elements, test all devices in the network (see Function test and Silence).
Device 1 remains in pairing mode for 3 minutes (the red LED flashes approximately once every 0.5 s). In this window, further devices can be connected one after another. Pairing mode can be ended manually by pressing the TEST/Silence button – the LED lights red for 3 seconds, then flashes green once and the device emits a short acoustic tone. As soon as device 1 leaves pairing mode, device 2 also leaves it and switches to normal operation.

Removing a device from the network

  1. On the device you want to remove from the network, press the TEST/Silence button 4× in succession (interval shorter than 1 s). The device emits a short acoustic tone and the LED indicator flashes red approximately once every 0.5 s.
  2. Press and hold the TEST/Silence button until the red LED indicator stops flashing, then release the button. The device emits a short acoustic tone and the LED flashes green once to indicate that it has been removed from the network.
If there are other devices in the network, they also emit a short acoustic tone and flash green once to indicate that one of the devices has been removed. Remove all devices in the network if you want to connect them to another wireless network.

Adding to the FireSafe app

A FireSafe Hub can be added to the wireless network, which, thanks to its internet connection, allows convenient setup and control of the whole system, including remotely, using the FireSafe app (for Android and iOS, and also in a PC version). The Hub monitors the operation of all connected FireSafe detectors and devices and immediately informs the user by push notifications if danger is detected.

Before you switch the Hub to pairing mode, make sure it is connected to the power supply and the internet network. If you connect to the Hub a device that is already part of a standalone wireless network, all devices in that network connect to the Hub at once.

Commissioning the FireSafe Hub

  1. Connect your smartphone to a Wi-Fi network.
  2. Install the FireSafe app on your phone from the App Store (iOS) or Google Play (Android).
  3. Connect the FireSafe Hub to the power supply.
  4. Connect the FireSafe Hub to the internet using an Ethernet cable (not included) or Wi-Fi.
  5. Launch the app and carry out the basic setup.
  6. In the app, tap the (+) button to add a device, scan the QR code on the back of the Hub and fill in the required details following the setup wizard.
  7. Confirm that the Hub has been added successfully in the app and tap the Save button.

Pairing the alarm with the Hub

  1. On the Hub, press the “PAIRING” button 3× briefly in succession (interval shorter than 1 s). The Hub's LED indicator flashes green approximately once every 0.5 s to indicate that the Hub has entered pairing mode. The mode can be ended by pressing the “PAIRING” button again.
  2. On the alarm you want to link, press the TEST/Silence button 3× briefly in succession (interval shorter than 1 s). The device emits a short acoustic tone and the green LED indicator flashes approximately once every 0.25 s to indicate pairing.
  3. After it has been added successfully, the alarm emits a short acoustic signal and the LED flashes green slowly for one minute, then switches to normal operation.
  4. To add another device, end the pairing of the previous device by pressing the TEST/Silence button and repeat step 2 with the new device. If the Hub's pairing interval (1 minute) expires, switch the Hub to pairing mode again (step 1).

States and signalling

LED indication / soundEvent
Short buzzer beep + red LED flashAlarm locked into the mounting bracket – automatic activation, a short initialisation follows
Green LED flashes 1× every 60 sStandby (operating) mode – everything is in order
Red LED flashes 1× per second + buzzer beeps 1× per second (repeatedly)A temperature rise in the range of 54–65 °C is detected – a fire alarm is raised and the device simultaneously sends a radio alarm signal to the other alarms in the network
3 long buzzer tones + red LED flashing (repeatedly)Alarm received from another alarm in the wireless network
Red LED flashes 1× per second, no acoustic signalTemporary alarm silencing active (using the TEST/Silence button or the IR remote control)
Red LED flashes 2× every 60 sDevice fault – the alarm is not functional; check and clean it and test it with the TEST/Silence button
Red LED flashes 1× every 60 s + buzzer beeps 1× every 60 sLow battery / end of life approaching – reported approx. 30 days before full depletion; the alarm must be replaced with a new one
The fire alarm can be temporarily silenced by pressing the button TEST/Silence on the alarm that raised the alarm, or by pressing any button on an ordinary IR remote control (SIC technology). Pressing the button on another alarm in the network silences the acoustic signal of all devices except the one that triggered the alarm. The silence lasts approx. 9 minutes, after which the alarm returns to alarm mode if the temperature has not fallen below the threshold value.

Choosing the installation location

This device is intended for use in ordinary indoor areas of residential units. For the highest level of fire protection, heat alarms should always be installed in combination with smoke alarms. Heat alarms are suitable for installation in areas such as boiler rooms, kitchens, laundry rooms, attics, lofts, garages or workshops, where high humidity, fumes, chemicals, dust or the presence of smoke particles pose a risk of false alarms from alarms based on optical detection technology. This heat alarm is also suitable for use in mobile homes and caravans.

Recommended placement of heat alarms in the home, room by room and floor by floor
Recommended placement of fire alarms (Figure 5-2-1)

Where and how not to install the alarm

National regulations on the number and placement of fire alarms may differ (see e.g. BS 5446-2). If in doubt, consult, for example, the fire and rescue service.

Ceiling installation

Install the heat alarm at least 300 mm from walls, light fittings or other obstructions. Mount it on the ceiling of the room at a distance of no more than 5.3 m from the farthest wall, 5.3 m from the door of the room in which a fire could start, and 5.3 m from the next heat alarm. When installing on sloping ceilings, the maximum distance required is 150 mm, measured vertically downwards from the apex of the highest point. The manufacturer recommends installing additional heat alarms as supplementary protection if the protected space is divided by closed doors or other obstructions that may impede effective fire detection or muffle the acoustic alarm signal.

Ceiling installation location – dead zone and maximum distances from walls and doors
Installation location (Figure 5-2-2 and 5-2-3)

Installation on a sloping ceiling

If you are installing the alarm on a sloping pitched or cathedral ceiling, place it within 900 mm of the highest point (measured horizontally from the higher side wall) and at least 150 mm from the apex of the highest point (measured vertically).

Installation location on a sloping pitched or cathedral ceiling
Installation location on a sloping ceiling (Figure 5-2-4)

Installing the alarm

Installation must be carried out by a competent person who is responsible for installing the device in accordance with applicable regulations. In case of doubt, turn to qualified professionals for installation or contact our technical support. When working at height, follow all safety procedures and use the required protective equipment.
  1. Choose a suitable location for installing the fire alarm (see Choosing the installation location).
  2. At the installation location, drill holes (⌀ 6 mm) using the mounting bracket. Insert wall plugs into the prepared holes.
  3. Fix the bracket with self-tapping screws.
  4. Stick the information label “CAUTION! – Battery is not replaceable, see user manual” in your language on the device.
  5. Insert the alarm into the mounting bracket and turn it clockwise until it locks into position.
Mounting the mounting bracket on the ceiling and fitting the alarm by turning it clockwise
Mounting the bracket and fitting the alarm (Figure 5-3-1 and 5-3-2)
Once the alarm is fixed in the mounting bracket, it activates automatically – this is confirmed by a short beep of the buzzer and a red flash of the LED. The device then initialises for a few seconds and automatically enters standby mode (green LED flashes once every 60 s). If you need to remove the alarm from the bracket, turn the device anticlockwise.

Function test and Silence

After installing the device, or during its regular maintenance, an alarm test must be carried out to prove its functionality.

Testing the device on its own

Briefly press the button TEST/Silence – the buzzer sounds a tone and the LED indicator flashes red, followed by a pause and then 2 consecutive beeps of the buzzer accompanied by a flash of the red LED, another pause and then one more repeat.

Testing a device linked in a wireless network

Press and hold the TEST/Silence button of any alarm connected in the network. The alarm emits a short acoustic tone with a flash of the red LED and sends a radio test mode signal. Keep the button pressed until the other alarms in the network also indicate test mode (short tone + alternating flashing of the green and red LED).

Testing devices connected via the FireSafe Hub

In the FireSafe app, select the device you want to test and press the “Test” button.

If any device emits no acoustic or visual signal during testing, check that it is correctly connected to the wireless network.

Temporary alarm silencing

In the event of a false alarm, the acoustic signal can be temporarily silenced by pressing the TEST/Silence button on the alarm that raised the alarm – this silences the acoustic signal of all devices in the network. Pressing the button on any other alarm silences the acoustic signal of all devices except the one that initiated the alarm. Temporary silencing is also possible using an IR remote control (SIC technology) – by pressing any button. The silence lasts 9 minutes, after which the alarm returns to alarm mode if the temperature has not fallen below the threshold value.

ProblemSolution
The alarm does not sound the buzzer during testingIf you are testing immediately after the first activation, wait a few seconds for the alarm to initialise. Make sure you have pressed the TEST/Silence button correctly.
The alarm chirps intermittentlyCheck that the device is correctly positioned (see Choosing the installation location) and carry out maintenance (see Maintenance).
The LED indicator flashes red and the buzzer beeps every 60 sThe alarm's battery is depleted – the alarm must be replaced with a new one immediately (see End of life).

If the device test is not completed successfully, send the alarm in for a warranty claim.

Maintenance

End of life

The SAFE 10YHT-RF alarm is powered by an integrated 3 V CR123A lithium battery, not user-replaceable, with a guaranteed life of more than 10 years of operation. The power battery is activated when the alarm is placed and locked into the mounting bracket.

If the battery capacity and voltage drop below the threshold value or the end of the device's life is approaching, the alarm signals this by flashing the red LED accompanied by a beep of the buzzer at regular 60-second intervals for 30 days before the battery is fully depleted.

POZOR – the battery in this device is built in and not replaceable. If the alarm's battery is depleted or the alarm's life has expired, replace the whole alarm with a new one.

The alarm must be replaced with a new one after 10 years from the date of installation – the replacement date is shown on the information label on the back of the alarm.

Technical specifications

Detection parameters
Detection typeTemperature rise, fault, low battery capacity
SensorClass A1 thermistor temperature sensor
MicroprocessorAI SAFE with predictive algorithm
Alarm at temperature range+54 °C to +65 °C (Class A1)
Measurement intervalRepeating 10 s cycle
Max. number of linked devices24 pcs
Signalling
Acoustic≥ 85 dB at a distance of 3 m
VisualLED indicator (red and green)
Silence functionYes – TEST/Silence button, IR remote control (SIC technology, not included in the package)
Silence timeapprox. 9 min
FireSafe CONNECTED wireless transmission
Operating frequency868 MHz
Communication typeTwo-way
Radio signal rangeUp to 1,000 m in open space
Max. number of linked devices24 FireSafe units
Interfaces and functions
ControlsTEST/Silence button
PCB protectionIZOVAX insulating and protective varnish layer with nanoparticles
Low battery / end-of-life warningYes
Mounting methodIndoor, ceiling only
General
ModelSAFE 10YHT-RF, white version
Power supply1× CR123A battery, 3 V, lithium (integrated, non-replaceable)
Current consumptionStandby mode ≤ 15 µA; in alarm ≤ 60 mA
Battery life / lifetime10 years
Operating temperature−10 °C to +55 °C
Operating humidity≤ 95 % RH (non-condensing)
Storage temperature / humidity−20 °C to +60 °C, 5–95 % RH (non-condensing)
Dimensions⌀ 93.8 mm × H 46.9 mm (with mounting bracket)
Weight115 g (with battery)
Housing materialPC + ABS
Housing colourWhite
Device life10 years from the date of installation
CompatibilityFireSafe Hub (e.g. SAFE 50HUB-WRF, SAFE 100HUB-WLRF)
CertificationBS 5446-2:2003 – Class A1 heat alarms
Declaration of ConformityCE, CE UKCA
EAN code0703123018234
Warranty10 years (on the device and battery)

Package contents

  1. Wireless heat alarm – 1 pc
  2. Self-tapping screw – 2 pcs
  3. Wall plugs – 2 pcs
  4. Mounting bracket – 1 pc
  5. User manual with a set of information labels – 1 pc

Safety notices

Safety habits and evacuation planning

What to do in the event of a fire alarm

Warranty

The manufacturer guarantees that the SAFE 10YHT-RF alarm will be free from defects in material and workmanship under normal use and operation for a period of ten years from the date of sale – the warranty covers both the device and the built-in battery. Under this warranty, the manufacturer's obligation is limited to repairing or replacing the alarm, or any of its defective parts, free of charge after the alarm has been sent, together with proof of the date of purchase, to the address of the SAFE HOME europe s.r.o. service centre, Čechova 1005/4, 750 02 Přerov, Czech Republic.

The warranty becomes void if the product has been damaged, altered, misused or modified after purchase, or if it has stopped working as a result of poor maintenance or incorrect placement. The warranty does not cover damage caused by failure to follow the instructions in this manual. This warranty does not affect your statutory rights.

In case of problems with the device, first contact technical support – most situations can be resolved remotely.

Need help?

SAFE HOME europe technical support:
E-mail: info@safe-home.eu  · Telephone: (+420) 581 222 262
Web: www.smart-safe.eu