SAFE 220 test spray is used to verify the functionality of smoke alarms. The test button on a smoke alarm does not check the sensor itself; it only verifies the condition of the batteries, the functioning of the electronic circuits and the correct triggering of the acoustic and visual signals. The actual function of the sensor can only be verified with a calibrated aerosol that faithfully simulates the presence of smoke.
Foreword
General
This user manual describes the function, principle and use of the SAFE 220 test spray for smoke alarms (hereinafter the “spray”). Read the manual carefully before using the spray and keep it for future reference.
Safety instructions
The following signal words may appear in the user manual:
| Signal word | Meaning |
|---|---|
| NEBEZPEČÍ | Indicates a high potential hazard which, if not avoided, may result in death or serious injury. |
| VAROVÁNÍ | Indicates a medium or low potential hazard which, if not avoided, could result in minor or moderate injury. |
| UPOZORNĚNÍ | Indicates a potential risk which could lead to property damage, data loss, reduced performance or an unpredictable result. |
| TIP | Provides methods to help you solve a problem or save time. |
| POZNÁMKA | Provides additional information, such as emphasis or a supplement to the text. |
Revision history
| Version | Revision content | Release date |
|---|---|---|
| V1.0.0 | First release. | September 2026 |
| V1.0.1 | Colours according to the FireSAFE brand (red). | October 2026 |
| V1.0.2 | Text edit. | October 2026 |
Privacy notice
As a user of the device or a data controller, you may collect the personal data of others, such as their face, fingerprints and licence plate number. You must comply with local privacy protection laws and regulations in order to protect the legitimate rights and interests of other people by taking measures which include, but are not limited to: providing clear and visible identification to inform people of the existence of the monitored area and providing the required contact information.
About the manual
- The user manual serves as a reference only. Minor differences may occur between the information provided and the product.
- We are not liable for damage resulting from use of the product in a manner that is not in accordance with the instructions in the user manual.
- The manual will be updated in line with the current laws and regulations of the relevant countries. For detailed information, see the printed user manual, scan the QR code or visit our website. The manual is for information purposes only. The electronic and printed versions may differ in minor details.
- All designs may be changed without prior written notice. As a result of product updates, certain differences may appear between the product and the information in the manual. The latest version of supplementary documentation is available from customer service.
- Printing errors or deviations may occur in the description of functions, operations and technical data. In case of doubt or dispute, we reserve the right of final interpretation. If the manual (in PDF format) cannot be opened, update your reader software or try another common reader.
- All trademarks, registered trademarks and company names in the manual are the property of their respective owners.
- If you encounter any problems when using the spray, visit our website, or contact your supplier or customer service.
- In case of ambiguity or dispute, we reserve the right of final interpretation.
Important precautions and warnings
This section contains information on correct handling of the product, prevention of risks and prevention of damage to property. Read it carefully before using the spray and follow the instructions provided while using it.
Safe use guidelines
- The test spray can is a pressurised container (aerosol) – protect it from direct sunlight and do not expose it to elevated temperatures.
- Do not puncture or burn the can, even after the contents have been used up.
- Use the spray exclusively for testing smoke alarms as described in this manual.
Functional elements
The SAFE 220 test spray consists of a seamless cylindrical can made of high-quality drawn aluminium, which ensures high durability and a long service life. The surface of the can is covered with a durable label with text and graphic information, including instructions for use. The upper part of the can has a conical top in which a valve is firmly fitted, followed by a plastic nozzle.
- Aluminium can containing test aerosol (220 ml)
- Durable label with instructions for use and additional information
- Valve with plastic nozzle in the conical upper part of the can
- Removable protective nozzle cap made of durable plastic
The spray is activated by simply pressing the nozzle, which releases the test aerosol. The total discharge time is approximately 75 s.
Principle of operation
The test button on a smoke alarm does not check the sensor itself; it only verifies the condition of the batteries, the functioning of the electronic circuits and the correct triggering of the acoustic and visual signals. Because the service life of the sensors in fire alarms can vary and is often unpredictable, manufacturers recommend regularly verifying their correct function using a special calibrated aerosol that faithfully simulates the presence of smoke.
Thanks to the specially developed composition of the aerosol particles in the SAFE 220 test spray, it is possible to faithfully imitate a wide range of real fire symptoms. The aerosol verifies the correct detection function of both optical and ionisation sensors in fire alarms and at the same time checks that their electronics and the whole system work reliably. It is the most widespread professional testing method, recognised worldwide and recommended by leading fire alarm manufacturers.
Alarm test procedure
- Shake the spray thoroughly before use.
- Point the nozzle at the sensor's inlet openings from a minimum distance of 50 cm.
- Briefly (1–2 seconds) press the nozzle to release a dose of test aerosol – do not use too much and do not spray too close to the detector.
- The alarm should trigger (acoustic and visual signalling) within 1 to 20 seconds.
- After verifying the function, silence the alarm in the usual way (using the TEST/Silence button on the alarm) and briefly ventilate the area.
What to do if the alarm does not respond
If the alarm does not trigger after the first attempt, repeat the test. If the repeated test does not trigger the alarm either, check the condition of the alarm's batteries or consider replacing it, as it may be faulty.
Storage
| Storage temperature | 0 °C to +50 °C |
|---|---|
| Storage humidity | 5 % to 95 % RH, non-condensing |
The test spray can is a pressurised container (UN 1950 – aerosols). Store it out of direct sunlight, in a dry place within the stated temperature range, and do not expose it to temperatures above +50 °C.
Technical specifications
Product dimensions
| Testing | |
| Test kit for | Smoke alarms |
| Carrying out the test | Performed by releasing test gas towards the detector |
| Gas dispensing time | 1–2 s |
| Kit capacity | More than 30 tests |
| Volume and packaging | |
| Volume | 220 ml |
| Product dimensions | 50 × 160 mm |
| Product weight | 133 g |
| Number of pieces per carton | 12 pcs |
| Carton dimensions | 208 × 180 × 160 mm |
| Carton weight | 1.74 kg |
| Environment | |
| Operating temperature | 0 °C to +50 °C |
| Operating humidity | Up to 95 % RH, non-condensing |
| Environment | Environmentally friendly |
| General | |
| UN number | 1950 |
| Declaration of Conformity | CE |
| Tested | EQC |
| EAN code | 0703123017473 |
| Warranty | Consumer product – see chapter Warranty |
Package contents
- SAFE 220 test spray (220 ml) with removable protective nozzle cap – 1 pc
Safety notices
- Before use, read these instructions and the label on the can carefully and keep them for future reference.
- The can is a pressurised container (aerosol, UN 1950 classification) – protect it from direct sunlight and do not expose it to temperatures above +50 °C.
- Do not puncture or burn the can, even after the contents have been used up.
- Shake the spray thoroughly before use; spray briefly (1–2 s) from a minimum distance of 50 cm from the alarm and do not use an excessive amount of aerosol.
- When used correctly in accordance with the instructions in this manual, the spray poses no health risk to people or pets.
- Use the spray exclusively for testing smoke alarms.
- Do not dispose of the product with general municipal waste – hand it in for recycling in accordance with local regulations.
Warranty
The SAFE 220 test spray is a consumable product with a limited life determined by the capacity of the can (more than 30 tests) and the storage conditions given in the chapter Storage. The warranty period will be provided by your seller or by SAFE HOME europe customer support.
In the event of problems with the appliance you are using the spray on, contact its manufacturer; in the event of problems with the spray itself, contact SAFE HOME europe technical support.
Need help?
SAFE HOME europe technical support:
E-mail: info@safe-home.eu · Telephone: (+420) 581 222 262