FireSAFE / Fire extinguishing sprays

Test kit for carbon monoxide detectors
SAFE 400

User manual

Updated 21 October 2026

Product page Datasheet (PDF)
SAFE 400 test kit for carbon monoxide (CO) detectors

SAFE 400 test kit is used to verify the operability of carbon monoxide (CO) detectors. The test button on a CO detector does not test the sensor; it only checks the batteries, electronic circuits and acoustic and visual signalling. The kit contains 400 ml (for 10 tests) of compressed calibrated gas in a can, simulating the presence of carbon monoxide.

400 mltest gas volume
10complete tests
3 sgas dispensing time
0 to +50 °Coperating and storage temperature
103 gproduct weight
C O Tests all CO detectors to EN 50291
Calibrated test gas
Lowest cost per test
For 10 complete tests
Test kit components under the can lid
Contains no harmful freons
Safe overall
Sensor and device operability test
Quick and easy to use

Foreword

General

This user manual describes the function, principle and use of the SAFE 400 test kit for carbon monoxide detectors (hereinafter the “kit”). Read the manual carefully before using the kit and keep it for future reference.

Safety instructions

The following signal words may appear in the user manual:

Signal wordMeaning
NEBEZPEČÍIndicates a high potential hazard which, if not avoided, may result in death or serious injury.
VAROVÁNÍIndicates a medium or low potential hazard which, if not avoided, could result in minor or moderate injury.
UPOZORNĚNÍIndicates a potential risk which could lead to property damage, data loss, reduced performance or an unpredictable result.
TIPProvides methods to help you solve a problem or save time.
POZNÁMKAProvides additional information, such as emphasis or a supplement to the text.

Revision history

VersionRevision contentRelease date
V1.0.0First release.September 2026
V1.0.1Colours according to the FireSAFE brand (red).October 2026
V1.0.2Text edit.October 2026

Privacy notice

As a user of the device or a data controller, you may collect the personal data of others, such as their face, fingerprints and licence plate number. You must comply with local privacy protection laws and regulations in order to protect the legitimate rights and interests of other people by taking measures which include, but are not limited to: providing clear and visible identification to inform people of the existence of the monitored area and providing the required contact information.

About the manual

Important precautions and warnings

This section contains information on correct handling of the product, prevention of risks and prevention of damage to property. Read it carefully before using the kit and follow the instructions provided while using it.

Safe use guidelines

UPOZORNĚNÍ

Functional elements

The SAFE 400 test kit consists of a can of test gas, a capillary tube and a practical foil bag that serves as an insulating enclosure. All the components needed to carry out the test are conveniently stored under the lid of the test gas can.

Principle of operation

The test button on a carbon monoxide (CO) detector does not test the sensor; it only checks the batteries, electronic circuits and acoustic and visual signalling. Because the service life of carbon monoxide detector sensors is often unpredictable, we recommend regularly verifying their operability using a calibrated gas that simulates the presence of carbon monoxide.

CO detectors do not trigger an alarm immediately – CO sensors are calibrated so that the detector triggers an alarm only from a certain CO concentration. The insulating enclosure (foil bag) is used to prevent the test gas from dispersing and instead create a constant concentration of gas around the sensor, which triggers the detector's alarm within a reasonable time.

If you have bought a CO detector to protect yourself and your loved ones, we recommend checking the sensor with the SAFE 400 test kit every six months.

Alarm test procedure

  1. Place the CO detector in the foil insulating enclosure.
  2. Fit the supplied capillary tube onto the plastic nozzle of the can.
  3. Insert the tube into the insulating enclosure containing the CO detector and seal the enclosure by pulling the ends of the drawstrings around its perimeter – do not remove the air that remains in the enclosure.
  4. Press the nozzle for 3 s.
  5. Withdraw the capillary tube and seal the enclosure again by pulling the drawstrings.
  6. The CO detector's sensor should trigger the alarm within 3 minutes.

What to do if the alarm does not respond

If the CO detector does not trigger the alarm, repeat the test after 15 minutes.

The SAFE 400 kit's source documents give no further specific procedure for the case where the CO detector does not respond even after a repeated test – in that case, follow the instructions in the operating manual of the CO detector concerned or contact its manufacturer.

Storage

Storage temperature0 °C to +50 °C
Storage humidity5 % to 95 % RH, non-condensing

The test gas can is a pressurised container (UN 1956 – compressed gas, n.o.s.). Store it out of direct sunlight, in a dry place within the stated temperature range, and do not expose it to temperatures above +50 °C.

Technical specifications

Product dimensions

Dimensions of the SAFE 400 test kit – 66 × 200 mm
Dimensions of the SAFE 400 test gas can (66 × 200 mm)
Testing
Test kit forCarbon monoxide and cigarette smoke detectors
Carrying out the testThe detector is tested inside the insulating bag
Gas dispensing time3 s
Kit capacity10 tests
Volume and packaging
Volume400 ml
Product dimensions66 × 200 mm
Product weight103 g
Number of pieces per carton24 pcs
Carton dimensions410 × 210 × 275 mm
Carton weight2.7 kg
Environment
Operating temperature0 °C to +50 °C
Operating humidityUp to 95 % RH, non-condensing
EnvironmentContains no harmful freons
General
UN number1956
Declaration of ConformityCE
TestedEQC
EAN code08595080009002
WarrantyConsumer product – see chapter Warranty

Package contents

  1. SAFE 400 can of calibrated test gas (400 ml) – 1 pc
  2. Capillary tube – 1 pc
  3. Foil insulating bag – 1 pc

Safety notices

Warranty

The SAFE 400 test kit is a consumable product with a limited life determined by the capacity of the can (10 tests) and the storage conditions given in the chapter Storage. The warranty period will be provided by your seller or by SAFE HOME europe customer support.

In the event of problems with the CO detector you are testing with the kit, contact its manufacturer; in the event of problems with the kit itself, contact SAFE HOME europe technical support.

Need help?

SAFE HOME europe technical support:
E-mail: info@safe-home.eu  · Telephone: (+420) 581 222 262
Web: www.smart-safe.eu