SAFE 400 test kit is used to verify the operability of carbon monoxide (CO) detectors. The test button on a CO detector does not test the sensor; it only checks the batteries, electronic circuits and acoustic and visual signalling. The kit contains 400 ml (for 10 tests) of compressed calibrated gas in a can, simulating the presence of carbon monoxide.
Foreword
General
This user manual describes the function, principle and use of the SAFE 400 test kit for carbon monoxide detectors (hereinafter the “kit”). Read the manual carefully before using the kit and keep it for future reference.
Safety instructions
The following signal words may appear in the user manual:
| Signal word | Meaning |
|---|---|
| NEBEZPEČÍ | Indicates a high potential hazard which, if not avoided, may result in death or serious injury. |
| VAROVÁNÍ | Indicates a medium or low potential hazard which, if not avoided, could result in minor or moderate injury. |
| UPOZORNĚNÍ | Indicates a potential risk which could lead to property damage, data loss, reduced performance or an unpredictable result. |
| TIP | Provides methods to help you solve a problem or save time. |
| POZNÁMKA | Provides additional information, such as emphasis or a supplement to the text. |
Revision history
| Version | Revision content | Release date |
|---|---|---|
| V1.0.0 | First release. | September 2026 |
| V1.0.1 | Colours according to the FireSAFE brand (red). | October 2026 |
| V1.0.2 | Text edit. | October 2026 |
Privacy notice
As a user of the device or a data controller, you may collect the personal data of others, such as their face, fingerprints and licence plate number. You must comply with local privacy protection laws and regulations in order to protect the legitimate rights and interests of other people by taking measures which include, but are not limited to: providing clear and visible identification to inform people of the existence of the monitored area and providing the required contact information.
About the manual
- The user manual serves as a reference only. Minor differences may occur between the information provided and the product.
- We are not liable for damage resulting from use of the product in a manner that is not in accordance with the instructions in the user manual.
- The manual will be updated in line with the current laws and regulations of the relevant countries. For detailed information, see the printed user manual, scan the QR code or visit our website. The manual is for information purposes only. The electronic and printed versions may differ in minor details.
- All designs may be changed without prior written notice. As a result of product updates, certain differences may appear between the product and the information in the manual. The latest version of supplementary documentation is available from customer service.
- Printing errors or deviations may occur in the description of functions, operations and technical data. In case of doubt or dispute, we reserve the right of final interpretation. If the manual (in PDF format) cannot be opened, update your reader software or try another common reader.
- All trademarks, registered trademarks and company names in the manual are the property of their respective owners.
- If you encounter any problems when using the kit, visit our website, or contact your supplier or customer service.
- In case of ambiguity or dispute, we reserve the right of final interpretation.
Important precautions and warnings
This section contains information on correct handling of the product, prevention of risks and prevention of damage to property. Read it carefully before using the kit and follow the instructions provided while using it.
Safe use guidelines
- The test gas can is a pressurised container (aerosol) – protect it from direct sunlight and do not expose it to elevated temperatures.
- Do not puncture or burn the can, even after the contents have been used up.
- Use the kit exclusively for testing carbon monoxide detectors as described in this manual.
Functional elements
The SAFE 400 test kit consists of a can of test gas, a capillary tube and a practical foil bag that serves as an insulating enclosure. All the components needed to carry out the test are conveniently stored under the lid of the test gas can.
- Can of calibrated test gas (400 ml, for 10 tests)
- Capillary tube that is fitted onto the can's nozzle
- Foil insulating bag with drawstrings, serving as an insulating enclosure
Principle of operation
The test button on a carbon monoxide (CO) detector does not test the sensor; it only checks the batteries, electronic circuits and acoustic and visual signalling. Because the service life of carbon monoxide detector sensors is often unpredictable, we recommend regularly verifying their operability using a calibrated gas that simulates the presence of carbon monoxide.
CO detectors do not trigger an alarm immediately – CO sensors are calibrated so that the detector triggers an alarm only from a certain CO concentration. The insulating enclosure (foil bag) is used to prevent the test gas from dispersing and instead create a constant concentration of gas around the sensor, which triggers the detector's alarm within a reasonable time.
Alarm test procedure
- Place the CO detector in the foil insulating enclosure.
- Fit the supplied capillary tube onto the plastic nozzle of the can.
- Insert the tube into the insulating enclosure containing the CO detector and seal the enclosure by pulling the ends of the drawstrings around its perimeter – do not remove the air that remains in the enclosure.
- Press the nozzle for 3 s.
- Withdraw the capillary tube and seal the enclosure again by pulling the drawstrings.
- The CO detector's sensor should trigger the alarm within 3 minutes.
What to do if the alarm does not respond
If the CO detector does not trigger the alarm, repeat the test after 15 minutes.
Storage
| Storage temperature | 0 °C to +50 °C |
|---|---|
| Storage humidity | 5 % to 95 % RH, non-condensing |
The test gas can is a pressurised container (UN 1956 – compressed gas, n.o.s.). Store it out of direct sunlight, in a dry place within the stated temperature range, and do not expose it to temperatures above +50 °C.
Technical specifications
Product dimensions
| Testing | |
| Test kit for | Carbon monoxide and cigarette smoke detectors |
| Carrying out the test | The detector is tested inside the insulating bag |
| Gas dispensing time | 3 s |
| Kit capacity | 10 tests |
| Volume and packaging | |
| Volume | 400 ml |
| Product dimensions | 66 × 200 mm |
| Product weight | 103 g |
| Number of pieces per carton | 24 pcs |
| Carton dimensions | 410 × 210 × 275 mm |
| Carton weight | 2.7 kg |
| Environment | |
| Operating temperature | 0 °C to +50 °C |
| Operating humidity | Up to 95 % RH, non-condensing |
| Environment | Contains no harmful freons |
| General | |
| UN number | 1956 |
| Declaration of Conformity | CE |
| Tested | EQC |
| EAN code | 08595080009002 |
| Warranty | Consumer product – see chapter Warranty |
Package contents
- SAFE 400 can of calibrated test gas (400 ml) – 1 pc
- Capillary tube – 1 pc
- Foil insulating bag – 1 pc
Safety notices
- Before use, read these instructions carefully and keep them for future reference.
- The can is a pressurised container (UN 1956 classification) – protect it from direct sunlight and do not expose it to temperatures above +50 °C.
- Do not puncture or burn the can, even after the contents have been used up.
- Always carry out the test inside the foil insulating enclosure, following the procedure in this manual.
- The kit contains no harmful freons or other ozone-depleting substances.
- Use the kit exclusively for testing carbon monoxide detectors.
- Do not dispose of the product with general municipal waste – hand it in for recycling in accordance with local regulations.
Warranty
The SAFE 400 test kit is a consumable product with a limited life determined by the capacity of the can (10 tests) and the storage conditions given in the chapter Storage. The warranty period will be provided by your seller or by SAFE HOME europe customer support.
In the event of problems with the CO detector you are testing with the kit, contact its manufacturer; in the event of problems with the kit itself, contact SAFE HOME europe technical support.
Need help?
SAFE HOME europe technical support:
E-mail: info@safe-home.eu · Telephone: (+420) 581 222 262
Web: www.smart-safe.eu